Four Saudi Aramco Engineering Standards decide most tag and marker choices on Aramco and Aramco-referenced projects. This guide sets out what each one means for the identification package, and where inspectors most often reject it.

SAES-B-067SAES-P-104SAES-J-004SAES-A-206
Refinery process tower with platforms and pipe racks

Scope. This is an engineering summary to help specify and budget tags. The binding text is the SAES revision named in your contract; check it, and the project specification, before issuing a submittal.

At a glance

StandardSubjectWhat it means for identification
SAES-B-067Safety identification and safety coloursPipe contents identification, safety colour coding, flow arrows, line numbers legible from grade and walkways
SAES-P-104Wiring methods and materialsDurable cable identification; adhesive, wrap-around and snap-on markers commonly not accepted outdoors in heavy industrial areas
SAES-J-004Instrument symbols and identificationInstrument tag numbering consistent with P&IDs; permanent instrument ID tags
SAES-A-206Positive material identification (PMI)Alloy verification of critical components; SS 316L (UNS S31603) tags and fittings traceable by certificate

SAES-B-067: pipe identification and safety colours

SAES-B-067 governs how pipe contents are identified: colour bands or markers by service, the legend, flow direction arrows, and line numbers that can be read from grade level and walkways. It also sets safety colours used across the plant. In practice the identification package must be planned against the project's piping line list so every line gets the right service colour and legend at the required locations.

The small-bore rule (< 2" / 52 mm)

Lines of 2" and above take stencilled or industrial adhesive markers. Lines under 2" get an embossed or engraved metal tag clamped to the pipe — at 80–90°C surface temperatures, adhesive markers on small diameters do not stay on. On a typical process unit this rule alone can account for hundreds of SS 316L tags in the BOQ, and it is often missed in early estimates.

Line sizeIdentification methodTypical tag spec
≥ 2" (≥ 52 mm)Stencilled or industrial adhesive markers with service legend and flow arrowPer SAES-B-067 colour table
< 2" (< 52 mm)Embossed / engraved metal tag clamped to the pipeSS 316L, 1.2–1.5 mm, SS band or wire fixing

SAES-P-104: cable and wire markers

Outdoors and in heavy industrial areas, adhesive wire markers, wrap-around labels and rigid snap-on markers lose grip or crack in heat and UV. Projects therefore specify tightly fitted slip-on markers inside panels, and SS 316L cable tags secured with SS 316L cable ties on outdoor cable runs, trays and junction box entries. Plastic cable ties degrade in UV and are not a substitute.

SAES-J-004: instrument identification

Instrument tags must carry the instrument number exactly as on the P&ID and loop drawings. Field instruments outdoors take SS 316L engraved tags wired to the instrument or its stand; panel-mounted instruments indoors can take engraved laminate labels.

SAES-A-206: PMI and SS 316L

Where positive material identification applies — critical, corrosive, offshore or hydrocarbon service — alloy components are verified (typically by XRF) against their specified grade. Stainless tags, chains and ties attached to those systems should be genuine 316L (UNS S31603) with mill certificates, so they do not become the odd item out during verification.

Traffolyte on Aramco plots

Rejected outdoors. Traditional phenolic Traffolyte warps at 80–100°C and chalks under UV within 2–5 years. Keep it to sheltered, air-conditioned control rooms, substations and MEP panels. Outdoor kiosks, local control stations and junction boxes take SS 316L or Metalphoto® anodized aluminum plates.

Checklist before the submittal

  • Tag and marker take-off reconciled to the line list, valve schedule, instrument index and cable schedule
  • Small-bore (< 2") lines counted separately for metal clamp tags
  • SS 316L grade, thickness and fixing stated, with mill certificates for PMI
  • No adhesive or plastic-tie cable markers in outdoor areas
  • Traffolyte limited to indoor, air-conditioned locations
  • Sample tags submitted with the material submittal

Send your tag schedule or BOQ

Excel/CSV tag schedules, P&ID valve lists or FAR asset counts — priced against SAES, ASME A13.1, BS 1710 or your corporate FAR spec. Email rfq@tagarabia.com.